36KV Indoor VCB Panel

With ABB Make VD4 CB


Horizontal Draw-out-Horizontal Isolation, IP4X STC: 25KA/3Sec, 31.5KA/3Sec, Busbar: Copper / Aluminium, up to 2000A Top Bushing (conductor connection), Incoming cum Outgoing/Cable in Cable Out, Multi Panel Switchboards

36KV Indoor VCB Panel

Technical Specification Of VCB


SR. NO. PARAMETER VALUE
1 Type Indoor, fixed Type
2 Rated Nominal Voltage (KV) 33KV
3 Rated Highest Voltage (KV) 36KV
4 Rated Normal Current (Amps) 1600 A
5 Rated Frequency (Hz) 50Hz
6 Rated Short Circuit Breaking Current (kA) 25 KA
7 Rated Short Circuit Making Current (kAp) 62.5 KAP
8 Rated PF Withstand Voltage for 1 minute 70 KV
9 Rated LI Withstand Voltage (KVP) 170 KVP
10 Rated Short Time Current (KA/Sec.) 25 KA / 3secs.
11 Rated Operating Sequence O – 0.3 sec., CO – 3 Min. – CO.
12 Rated Aux. Supply for Spring charging Motor 110/230V AC / DC
13 Spring charging motor Rating 110/230V AC / DC, 250 W
14 Spring charging motor time (ms) < 10 Sec.
15 Detail of overload Protection Provided for spring charging motor MCB / Fuse
16 Rated supply of Tripping / Closing Coils 24 / 30 / 110 /220 V DC
17 Power Required for Tripping & Closing Coils 250 W
18 No. of Poles 3
19 No. of Breaks / Pole 1
20 Class Indoor
21 Application Standards IEC- 62271-100 , IEC- 62271-200 & IS 3427-1997
22 Type of Operating Mechanism Motor Wound Spring Charged stored energy
23 VACUUM INTERRUPTER DETAILS

a) Make
b) Model No. / Type, Designation
c) Voltage / Current Rating
d) STC Rating & Duration
e) Type of Contacts
f) Contact Pressure at no Load
g) Electrical Life

i) At rated normal current
ii) At rated short circuit current withstand
h) Mechanical life
 

Shaanxi / CGL / Equivalent approved make
TD-27/TD-17/VL-35416-13F/ Equ.
36 KV, 2000A
25 KA / 3Sec.
Butt
170 kgf to 230 kgf
 

10000 operations
100 operations
20000 operations
24 Maximum Temp. Rise over ambient Temp. Within permissible limits as per IS / IEC
25 Breaking capacity (KA)

a) Symmetrical
b) Symmetrical at rated service voltage
 

25KA
25KA
26 Minimum closing time from the instant of trip coil energisation (ms) > 80 ms
27 Rated transient recovery voltage As per std.
28 a) Data on re-striking voltage  

i) Amplitude factor 100% & 50% of rated capacity
ii) Natural frequency
iii) Phase factor
iv) R.V. Volts / micro second
As per std. 

As per std.

50 Hz
As per IEC – 62271-100
As per std.
29 Minimum clearance in air (MM)  

i) Phase to Phase (C to C)
ii) Phase to Earth
iii) Live parts to ground level
 

300 mm
300 mm
300 mm
30 Total length of break per phase 19 ±2 mm
31 Total Break Time (milli-sec.) < 5o ms
32 Opening Time (milli-sec) < 5o ms
33 Closing Time (milli-sec) < 8o ms
34 Opening Speed (Meter / Sec.) 0.8 to 1.4 M/Sec.
35 Closing Speed (Meter / Sec.) 0.8 to 1.4 M/Sec.
36 DC component of rated short circuit breaking current > 50 %
37 First pole to clear factor > 50 %
38 Number of Auxiliary contact provided & type

i) Normally open
ii) Normally close
iii) Those adjustable with respect to the position of main contacts
 

6 No
6 NC
Yes

39 Weight of VCB with Mechanism. 350 Kgs Approx.
40 Overall dimension of VCB (mm) 960x632x1575
41 Measures provided to indicate for Wear / tear of contacts Cont. Erosion mark on interrupter.